-40%
Fluke 1732/EUS Three-Phase Electrical Energy Logger with current probes
$ 1960.45
- Description
- Size Guide
Description
Untitled DocumentFluke 1732/EUS Three-Phase Electrical Energy Logger with current probes
Model:
1732/EUS
| Order No:
1732/EUS
Designed to find sources of electrical energy waste, which allows the user to locate when and where energy in your facility is being consumed; from the service entrance to individual circuits. Additionally, the Energy Analyze software package allows users to compare multiple data points over time and comes with current probes.
Brand:
Fluke
Model:
1732/EUS
Order No:
1732/EUS
Condition:
NEW
Description
Fluke 1732/EUS Three-Phase Electrical Energy Logger with current probes
Three-phase power measurements made easy
Deliver easy to use three-phase power measurement data for locating sources of electrical energy waste, overloaded circuits and help users do routine load studies. Find out when and where energy in your facility is being used - from the service entrance to individual circuits. This electrical energy logger is Fluke Connect compatible which allows users to access and share three-phase power data remotely with their team so they can maintain safer working distances and make critical decisions in real-time, minimizing the need for protective equipment, site visits, and check-ins.
Profiling energy usage across your facility helps you identify opportunities for energy savings, and provides you with the data you need to act on them. The Energy Analyze software package allows you to compare multiple data points over time to build a complete picture of energy usage, which is the first step to reduce the cost of your energy bill.
Features
Key measurements: automatically capture and log voltage, current, power, power factor, energy and associated values
Fluke Connect® compatible: view data locally on the instrument, via Fluke Connect mobile app and desktop software or through your facilities' WiFi infrastructure
Convenient instrument powering: power instrument directly from the measured circuit
Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
Measure all three phases
Comprehensive logging: more than 20 separate logging sessions can be stored on the instruments
Optimized user interface: quick, guided, graphical setup ensures you're capturing the right data every time, and the intelligent verification function indicates correct connections have been made, reducing user uncertainty
Bright, color touch screen: perform convenient in-the-field analysis and data checks with full graphical display
Optimized user interface: capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function
Complete "in-the-field" setup through the front panel or Fluke Connect: no need to return to the workshop for download and setup or to take a computer to the electrical panel
Energy Analyze Plus application software: download and analyze every detail of energy consumption with our automated reporting
Applications
Energy studies - full range of electrical power and energy parameters
Load studies - simple current only logging for load sizing
General facilities staff
Facilities engineers
Building managers concerned with energy costs
Residential/commercial electricians
Energy consultants
Included
Energy Logger
Voltage Test Leads
4 x Alligator Clips
3 x Flexible Current Probe
Line Cords
Carrying Case
Power Supply
Color Coding Set
Specifications
Voltage
Range
1000 V
Resolution
0.1 V
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.2% + 0.01%)
Current: Direct Input i17xx-flex 1500 12"
Range
150 A
1500 A
Resolution
0.1 A
1 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.02%)
±(1% + 0.02%)
Current: Direct Input i17xx-flex 3000 24"
Range
300 A
3000 A
Resolution
1 A
10 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.03%)
±(1% + 0.03%)
Current: Direct Input i17xx-flex 6000 36"
Range
600 A
6000 A
Resolution
1 A
10 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1.5% + 0.03%)
±(1.5% + 0.03%)
Current: Direct Input i40s-EL Clamp
Range
4 A
40 A
Resolution
1 mA
10 mA
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.7% + 0.02%)
±(0.7% + 0.02%)
Frequency
Range
42.5 to 69 Hz
Resolution
0.01 Hz
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.1%)
Auxillary Input
Range
±10 V dc
Resolution
0.1 mV
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.2% + 0.02%)
Voltage Min/Max
Range
1000 V
Resolution
0.1 V
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.1%)
Current Min/Max
Range
Defined by accessory
Resolution
Defined by accessory
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(5% + 0.2%)
THD on Voltage
Range
1000%
Resolution
0.1%
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±0.5
THD on Current
Range
1000%
Resolution
0.1%
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±0.5
Power Supply
Voltage Range
100 to 500 V using safety plug input when powering from the measurement circuit
100 to 240 V using standard power cord (IEC 60320 C7)
Power Consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency
≥68.2% (in accordance with energy efficiency regulations)
Maximum No-Load Consumption
≤0.3 W only when powered using IEC 60320 input
Mains Power Frequency
50/60 Hz ±15%
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-Battery Runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging Time
<6 hours
Data Acquisition
Resolution
16-bit synchronous sampling
Sampling Frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input Signal Frequency
50/60 Hz (42.5 to 69 Hz)
Circuit Types
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT
3-φ wye balanced, 3-φ Aron/Blondel (2-element delta)
3-φ delta open leg, Currents only (load studies)
Data Storage
Internal flash memory (not user replaceable)
Memory Size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events
Basic Interval
Measured Parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging Interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging Time Min/Max Values
Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured Parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Standards Compliance
Power
IEEE 1459
Interfaces
USB-A
File transfer via USB flash drive, firmware updates max. current: 120 mA
WiFi
File transfer and remote control via direct connection or WiFi infrastructure
USB-Mini
Data download device to PC
Voltage Inputs
Number of Inputs
4 (3 phases and neutral)
Maximum Input Voltage
1000 Vrms, CF 1.7
Input Impedance
10 M&ohm
Bandwidth (-3 dB)
42.5 Hz to 3.5 kHz
Scaling
1:1 and variable
Measurement Category
1000 V CAT III/600 V CAT IV
Current Inputs
Number of Inputs
3, mode selected automatically for attached sensor
Input Voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski Coil Input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)
42.5 Hz to 3.5 kHz
Scaling
1:1 and variable
Auxiliary Inputs
Number of Inputs
2
Input Range
0 to ±10 V dc, 1reading/s
Scale Factor
Format: mx + b (gain and offset) user configurable
Displayed Units
User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of Inputs
2
Supported Modules
Fluke Connect® 3000 series
Acquisition
1 reading/s
Environmental Specifications
Operating Temperature
14 to 122 °F (-10 to 50°C)
Storage Temperature
-4 to 140°F (-20 to 60°C)
With battery: -4 to 122 °F (-20 to 50°C)
Operating Humidity
50 to 86°F (10 to 30°C) max. 95% RH
86 to 104°F (30 to 40°C) max. 75% RH
104 to 122°F (40 to 50 °C) max. 45% RH
Operating Altitude
6561.7' (2000 m) [up to 13,123.4' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV]
Storage Altitude
39,370' (12,000 m)
Enclosure
IP50 in accordance with EN60529
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Safety
IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic Compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature Coefficient
0.1 x accuracy specification/°C
General Specifications
Color LCD Display
4.3" (109 mm) active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Dimensions
Instrument: 7.8 x 6.6 x 2.2" (198 x 167 x 55 mm)
Power supply: 5.1 x 5.1 x 1.8" (130 x 130 x 45 mm)
Instrument with power supply attached: 7.8 x 6.6 x 3.5" (198 x 167 x 0.9 mm)
Weight
Instrument: 2.5 lbs (1.1 kg)
Power supply: 0.9 lb (400 g)
Terms & Conditions
Item Condition:
Unless specified otherwise all products listed are Brand New in the original factory packaging and include a full factory warranty.
Shipping:
We currently only ship to U.S. buyers. We ship items within one or two business days from payment. We do not process shipments on weekends and holidays. Local pick up is not available. We only ship to addresses verifiable by either PayPal or credit card issuing bank.
Please note that we cannot alter the address once a purchase is made. In the case of PayPal payment, we will ship orders when the payment is marked “Eligible” for PayPal Seller’s protection.
*Shipping Rates are for Continental US, Please Contact us for other US Destinations
Payment:
Currently all payments must be made directly though PayPal
Sales Tax:
We are required to charge sales tax in North Carolina
Return Policy:
If for any reason you are not 100% satisfied with a product you receive from us, you may return the regular stock product within 30 days from the time of receipt, for a full refund or exchange of the product you purchased (less any shipping costs). Within this time, products may be returned; freight prepaid and must be in their original packaging and in resalable condition.
Shipping errors, missing items or damages must be reported to us immediately (damages should be accompanied by a signed bill of lading acknowledging the damage). Items returned will be inspected for damage or misuse at which time they may be subject to restocking fees, other fees or refused, prior to the issuance of any credit.