Product overview: Fluke 1732 and 1734 Three Phase Power Measurement Logger
Three phase power measurements made easy
The Fluke 1732 (without wifi) and 1734 (with wifi) Three Phase Electrical Energy Loggers deliver easy to use three phase power measurement data for discovering sources of electrical energy waste, overloaded circuits and help you perform routine load studies. Discover when and where energy in your facility is being consumed - from the service entrance to individual circuits. Access and share three phase power data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins.
Profiling energy usage across your facility helps you identify opportunities for energy savings, and provides you with the data you need to act on them. The new Energy Analyze software package allows you to compare multiple data points over time to build a complete picture of energy usage, which is the first step to reduce the cost of your energy bill.
Key measurements:
Automatically capture and log voltage, current, power, power factor, energy and associated values
Fluke Connect® compatible:
View data locally on the instrument, via Fluke Connect mobile app and desktop software or through your facilities’ WiFi infrastructure
Convenient instrument powering:
Power instrument directly from the measured circuit
Highest safety rating in the industry:
600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
Measure all three phases:
With included 3 flexible current probes
Comprehensive logging:
More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis
Optimized user interface:
Quick, guided, graphical setup ensures you’re capturing the right data every time, and the intelligent verification function indicates correct connections have been made, reducing user uncertainty
Bright, color touch screen:
Perform convenient in-the-field analysis and data checks with full graphical display
Complete “in-the-field" setup through the front panel:
No need to return to the workshop for download and setup or to take a computer to the electrical panel
Fully integrated logging:
Connect other Fluke Connect devices to the Fluke 1734 to simultaneously log up to two other measurement parameters, virtually any parameter available on a Fluke Connect wireless digital multimeter or module*
Energy Analyze Plus application software:
Download and analyze every detail of energy consumption with our automated reporting
Which three-phase logger is right for you?
Three-phase Energy Loggers
Three-phase Power Loggers
Features
1732 Energy Logger
1734 Energy Logger
1736 Power Logger
1738 Advanced Power Logger
Load studies
•
•
•
•
Energy assessments
•
•
•
•
Neutral Current, 4th current channel
•
•
Harmonics measurements
•
•
Voltage event capture
•
•
PQ Health Graphical
overview (EN50160)
Upgrade package*
•
IEEE519 total harmonic distortion
Optional
Optional
Fully integrated logging with Fluke Connect®
Upgrade package*
•
Upgrade package*
•
WiFi
Optional
•
•
•
Wi-Fi / Bluetooth
Optional
•
Optional
•
Magnetic probe set
Optional
•
Optional
•
Magnetic hanger
Optional
•
Optional
•
Connection via WiFi router
Requires FREE software license available upon product registration.
Requires FREE software license available upon product registration.
Specifications
Accuracy
Parameter
Range
Resolution
Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
Voltage
1000 V
0.1 V
±(0.2% + 0.01%)
Current: Direct input
i17xx-flex 1500 12"
150 A
0.1 A
±(1% + 0.02%)
1500 A
1 A
±(1% + 0.02%)
i17xx-flex 3000 24"
300 A
1 A
±(1% + 0.03%)
3000 A
10 A
±(1% + 0.03%)
i17xx-flex 6000 36"
600 A
1 A
±(1.5% + 0.03%)
6000 A
10 A
±(1.5% + 0.03%)
i40s-EL clamp
4 A
1 mA
±(0.7% + 0.02%)
40 A
10 mA
±(0.7% + 0.02%)
Frequency
42.5 Hz to 69 Hz
0.01 Hz
±(0.1%)
Auxillary input
±10 V dc
0.1 mV
±(0.2% + 0.02%)
Voltage min/max
1000 V
0.1 V
±(1% + 0.1%)
Current min/max
Defined by accessory
Defined by accessory
±(5% + 0.2%)
THD on voltage
1000%
0.1%
±0.5
THD on current
1000%
0.1%
±0.5
Intrinsic Uncertainty ±(% of reading +% of range)¹
Parameter
Influence quantity
iFlex1500-12
iFlex3000-24
iFlex6000-36
i40S-EL
150 A / 1500 A
300 A / 3000 A
600 A / 6000 A
4 A / 40 A
Active Power P
PF = 0.99
1.2% + 0.005%
1.2% + 0.0075%
1.7% + 0.0075%
1.2% + 0.005%
Active Energy Ea
PF = 0.99
1.2% + 0.005%
1.2% + 0.0075%
1.7% + 0.0075%
1.2% + 0.005%
Apparent power S
0 = PF = 1
1.2% + 0.005%
1.2% + 0.0075%
1.7% + 0.0075%
1.2% + 0.005%
Apparent Energy Eap
0 = PF = 1
1.2% + 0.005%
1.2% + 0.0075%
1.7% + 0.0075%
1.2% + 0.005%
Reactive power Q
0 = PF = 1
2.5% of measured apparent power
Reactive Energy Er
0 = PF = 1
2.5% of measured apparent power
Power Factor PF
-
±0.025
Displacement Power Factor
-
±0.025
DBF/cos?
-
±0.025
Additional uncertainty in% of range¹
VP-N>250 V
0.015%
0.0225%
0.0225%
0.015%
¹Range = 1000 V x Irange
Reference conditions:
Environmental:
23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
Input conditions:
Cos?/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
Current and power specifications:
Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of Irange
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient:
Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Electrical Specifications
Power Supply
Voltage range
100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency
= 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption
< 0.3 W only when powered using IEC 60320 input
Mains power frequency
50/60 Hz ±15%
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time
< 6 hours
Data Acquisition
Resolution
16-bit synchronous sampling
Sampling frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency
50/60 Hz (42.5 to 69 Hz)
Circuit types
1-f, 1-f IT, Split phase, 3-f delta, 3-f wye, 3-f wye IT, 3-f wye balanced, 3-f Aron/Blondel (2-element delta), 3-f delta open leg, Currents only (load studies)
Data storage
Internal flash memory (not user replaceable)
Memory size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
¹The number of possible logging sessions and logging period depends on user requirements.
Basic Interval
Measured parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values
Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Standards Compliance
Power
IEEE 1459
Interfaces
USB-A
File transfer via USB flash drive, firmware updates
Max. current: 120 mA
WiFi
File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1734, or 1732 upgrade option)
USB-mini
Data download device to PC
Voltage Inputs
Number of inputs
4 (3 phases and neutral)
Maximum input voltage
1000 Vrms, CF 1.7
Input impedance
10 MO
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Scaling
1:1 and variable
Measurement category
1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs
3, mode selected automatically for attached sensor
Input voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Scaling
1:1 and variable
Auxiliary Inputs
Number of inputs
2
Input range
0 to ±10 V dc, 1reading/s
Scale factor (available 2014)
Format: mx + b (gain and offset) user configurable
Displayed units (available 2014)
User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of inputs
2
Supported modules
Fluke Connect® 3000 series
Acquisition
1 reading/s
Environmental Specifications
Operating temperature
-10 °C to +50 °C (14 °F to 122 °F)
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity
10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude
12,000m
Enclosure
IP50 in accordance with EN60529
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Safety
IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature coefficient
0.1 x accuracy specification/°C
General Specifications
Color LCD display
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty
Instrument and power supply: Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions
Instrument: 19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in)
Power supply: 13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in)
Instrument with power supply attached: 19.8 x 16.7 x 9 cm (7.8 x 6.6 x 3.5 in)
Weight
Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection
Kensington lock slot
i17xx-flex 1500 12" Flexible Current Probe Specifications
Measuring range
1 to 150 A ac/10 to 1500 A ac
Nondestructive current
100 kA (50/60 Hz)
Intrinsic error at reference condition*
±0.7% of reading
Accuracy 173x + iFlex
±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range
0.05% of reading/°C 0.09% of reading/°F
Working voltage
1000 V CAT III, 600 V CAT IV
Probe cable length
305 mm (12 in)
Probe cable diameter
7.5 mm (0.3 in)
Minimum bending radius
38 mm (1.5 in)
Output cable length
2 m (6.6 ft)
Weight
115 g
Probe cable material
TPR
Coupling material
POM + ABS/PC
Output cable
TPR/PVC
Operating temperature
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating
-40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating
15% to 85% non-condensing
IP rating
IEC 60529:IP50
* Reference condition:
Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
Primary conductor in center position
Included Accessories:
1732 Energy Logger
Power supply
Voltage test leads
Alligator clips (4x)
12 in 1,500A flexible current probe (3x)
Soft case
Energy Analyze Plus software
Line cords
Color coding set
Condition:
NEW
Auction Details:
Shipping:
All
domestic
packages will be shipped out via Fedex, UPS, or USPS within the lower 48 states
Shipping to Hawaii, Alaska, Puerto Rico costs extra, message us for shipping quote and those shipments will be shipped out via USPS priority mail, unless otherwise stated in the auction or negotiated in emails.
Shipping to APO, RR, or PO box will be handled via USPS and would be extra on certain items, please email us prior bidding.
Goods will be dispatched the latest in
2
business days.
Goods will be shipped out after the holidays and weekends.
No local pick
ups accepted at this time, unless otherwise stated in the auction
Shipping costs are set at that price to cover some of our costs and packaging and handling fees as well as some of the ebay and paypal fees which add to about 13% of the total end price. Please don't email us to negotiate about the shipping costs. We are extremely busy, so we might not answer your emails.
Shipping and handling fees are not negotiable, by bidding on this item the buyer agrees to pay for all the shipping costs
We ship to any destination in the world.
INTERNATIONAL BUYERS:
The International shipping rate is flat rate to most destinations in the world, please email us for additional information.
California buyers are subject to pay 9% tax.
International buyers are responsible for all tax and custom duty charges outside the country.
Payment:
U.S. Buyers:
Credit cards through PayPal
Please note that we can't accept direct credit card payments at this time
International Buyers:
PayPal or Wire
Payment is due within 6 days of auction closing.
If payment is not received within this time unless otherwise stated or negotiated, item will be relisted on eBay.
Terms & Conditions:
After the auction is closed,
auction winners should contact us regarding any questions or requests.
After the auction is closed, payment should be received within 6 days.
Buyer has 30 days to return the product, return product should be brand new with all original accessories, buyer pays shipping costs.
Shipping and handling charges are not returnable
Items will be replaced or exchanged in case of DOA
If the same item or similar item is not in stock in case of DOA, the buyer will receive a refund back
We combine shipping to save customers money, however, there will be an additional charge per item, please read the description for each item to find out about the specific fees.
All buyers are subject to pay all taxes and duty fees inside and outside of the United States,
Our facilities are closed during the weekends and other holidays and there will be no shipments during these time periods. All packages will go out after the weekend or after the holidays.
Contact Information:
Please use ebay message